HVAC systems: measurements of airflows in small duct length
DOI: https://doi.org/10.20528/cjsmec.2016.11.027
View Counter: Abstract | 1468 times | ‒ Full Article | 248 times |
Full Text:
PDFAbstract
One of the most feasible ways to measure duct airflows is by tracer gas techniques, especially for complex situations when the duct lengths are short as well as their access, which makes extremely difficult or impossible other methods to be implemented. One problem associated with the implementation of tracer gas technique when the ducts lengths are short is due to the impossibility of achieving complete mixing of the tracer with airflow and its sampling. In this work, the development of a new device for the injection of tracer gas in ducts is discussed as well as a new tracer-sampling device. The developed injection device has a compact tubular shape, with magnetic fixation to be easy to apply in duct walls. An array of sonic micro jets in counter current direction, with the possibility of angular movement according to its main axle ensures a complete mixing of the tracer in very short distances. The tracer-sampling device, with a very effective integration function, feeds the sampling system for analysis. Both devices were tested in a wind tunnel of approximately 21m total length. The tests distances between injection and integration device considered were: X/Dh=22; X/Dh=4; X/Dh=2; and X/Dh=1. For very short distances of X/Dh=2 and X/Dh=1, semi empirical expressions were needed. A good reproducibility of airflow rate values was obtained. These preliminary tests showed that the practical implementation of tracer gas techniques in HVAC systems for measuring airflow rates with a very short mixing distance is possible with the devices developed.
Keywords
References
ANSY/ASHRAE Standard 111-118 (1988). Practices for measurement, testing, adjusting and ba1ancing of building heating, ventilation, air conditioning and refrigeration systems, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta.
Carter G (1998). Tracer Gas Air Flow Rate Measurement as an Alternative to Pitot Tube Traverse in Commercial Building Ventilation Systems, M.Sc. thesis, UC Berkeley, Berkeley.
Center for Environmental Design Research (2003). College of Environmental Design, UC Berkeley, Berkeley.
Cheong K (1994). The Application of Tracer-Gas Techniques for Measuring Airflow in HVAC Systems. PhD thesis, School of the Built Environment, University of Nottingham, Nottingham, UK.
Cheong KW (1996). Tracer gas technology for airflow measurements in HVAC systems. International Journal of Energy Research, 20(12), 1081-1094.
Cheong KW (2001). Airflow measurements for balancing of air distribution system-tracer-gas technique as an alternative. Building and Environment, 36.
Cheong KW, Chong KY (2000). Development and application of an indoor air quality audit to air-conditioned building in Singapore. Building and Environment.
Cheong KW, Rifat SB (1992). Application of tracer-gas techniques for measurement of friction-factors of rectan-gular ducts. Air Infiltration Review, 13.
FlowMarker lnstructions Manual (2001). Günther Schaidt Safex Chemie.
Grieve PW (1989). Measuring Ventilation Using Tracer-gases, Brüel and Kjaer.
Indoor Climate and Ventilation (2001). Measurement of main air flows using tracer gases. Dantec Dynamics Ap-plication Note.
INNOVA Air Tech Instruments (1998). Monitor Multigaz Type l3l2 Instructions.
International Standard ISO 3966. Mesure du Débit des Fluides dans les Conduites Fermées-Méthode d' Exploration du Champs des Vitesses au moyen de Tubes de Pitot Doubles", International Standards Organisation, Genève.
International Standard ISO 4053/I-1977 (F). Mesurage de Débits de Gaz dans les Conduites - Méthodes par.
McWilliams (2003). Review of airflow measurement techniques, energy performance of buildings group, Envi-ronmental Energy Technologies Division, Lawrence Berkeley National Laboratory, Berkeley.
Rifat SB (1990). Comparison of tracer gas techniques for measuring airflow in ducts. Journal of the Institute of Energy, 63.
Rifat SB, Cheong KW (1993). Tracer-gas techniques for design and commissioning of HVAC system. Proceedings of First International Conference on Environmental Engineering, Leicester, UK.
Rifat SB, Lee SF (1990). Turbulent flow in duct: Measurement by a tracer gas technique. Building Services Engi-neering Research and Technology, 11.
Silva AR (2002). Medição de Caudais de Ar pelo Método de Emissão Constante com Desenvolvimento de Sonda para Gás Traçador. Ph.D. Thesis, INETI, Lisboa.
Traceurs-Partie I: Généralités, International Standards Organisation, Genève.
Viegas DX (1981). Uma Técnica de Erosão Aplicada ao Estudo da Interação de Jatos Turbulentos com uma Superfície Plana. Ph.D. Thesis. Faculdade de Ciências e Tecnologia da Universidade de Coimbra, Portugal.
---
Peer-review under responsibility of the organizing committee of ICEM17.
Refbacks